Main demand configuration view – Rockwell Automation Energy Management Accelerator Toolkit Quick Start User Manual
Page 382

382
Rockwell Automation Publication IASIMP-QS016C-EN-P - October 2014
Chapter 12 Demand Control
Main Demand Configuration View
Click on the wrench button from the toolbar to display the load configuration view.
Faceplate Toolbar
Peak Demand
Start/Stop Time
Peak Demand Days
Button
Icons
Description
Alarm
The alarm button indicates an alarm condition and activates alarm diagnostic views. A grey bell indicates normal
status, with no alarms. A red flashing bell indicates an alarm condition.
Load Configuration
The Load Configuration button displays the load configuration screen. (The load configuration screen can also be
displayed by clicking a load number from any of the status screens and entering the correct password.)
Home
The Home button lets you view the status of all 16 loads.
Help
The Help button provides information for the existing view.
Close
Click the Close button to close the faceplate.
Days of the Week
Click on a day of the week to toggle demand control on/off for that day.
Demand Control
Schedule
Click on the Start Time or Stop Time Hour or Minute to launch the keypad input object and enter a time.
Predicted KW
Demand
The predicted kW demand is read from the PowerMonitor device and displayed here for status only. (The color
indication is the same as described for the demand control status screen.)
Present Billing KW
Demand
The present billing kW demand is equal to the max of interval demands during the on-peak time-of-use periods in
the current billing month. (The color indication is the same as described for the demand control status screen.)
Demand KW
Setpoint
Click on the demand setpoint to launch the numeric keypad and enter the demand kW setpoint.
Billing End Date
Click on the billing end date to launch the numeric keypad and enter the monthly billing end date. (This date is used
to calculate the present billing kW demand for the current billing month.)
Time and Date
The current time and date are displayed in the lower right corner of the faceplate.