Main demand configuration view – Rockwell Automation Energy Management Accelerator Toolkit Quick Start User Manual

Page 382

Advertising
background image

382

Rockwell Automation Publication IASIMP-QS016C-EN-P - October 2014

Chapter 12 Demand Control

Main Demand Configuration View

Click on the wrench button from the toolbar to display the load configuration view.

Faceplate Toolbar

Peak Demand
Start/Stop Time

Peak Demand Days

Button

Icons

Description

Alarm

The alarm button indicates an alarm condition and activates alarm diagnostic views. A grey bell indicates normal

status, with no alarms. A red flashing bell indicates an alarm condition.

Load Configuration

The Load Configuration button displays the load configuration screen. (The load configuration screen can also be

displayed by clicking a load number from any of the status screens and entering the correct password.)

Home

The Home button lets you view the status of all 16 loads.

Help

The Help button provides information for the existing view.

Close

Click the Close button to close the faceplate.

Days of the Week

Click on a day of the week to toggle demand control on/off for that day.

Demand Control

Schedule

Click on the Start Time or Stop Time Hour or Minute to launch the keypad input object and enter a time.

Predicted KW

Demand

The predicted kW demand is read from the PowerMonitor device and displayed here for status only. (The color

indication is the same as described for the demand control status screen.)

Present Billing KW

Demand

The present billing kW demand is equal to the max of interval demands during the on-peak time-of-use periods in

the current billing month. (The color indication is the same as described for the demand control status screen.)

Demand KW

Setpoint

Click on the demand setpoint to launch the numeric keypad and enter the demand kW setpoint.

Billing End Date

Click on the billing end date to launch the numeric keypad and enter the monthly billing end date. (This date is used

to calculate the present billing kW demand for the current billing month.)

Time and Date

The current time and date are displayed in the lower right corner of the faceplate.

Advertising