FactoryTalk View ME Energy Faceplates
Chapter 11
Configure PowerMonitor Status Input Faceplate AOIs
Logic is required to display energy meter data on Equipment Status and Alarm History faceplates from PowerMonitor
status inputs.
1. Open your program routine and create a new rung.
2. Click the Add-On tab, then click
the required PowerMonitor status
input Add-On Instruction to add
to the rung.
For this example, the
Energy_Gas_PM_Status
instruction is selected to support
the Gas Main meter connected to
the MCC 2 PowerMonitor status
input.
3. Click in the PowerMonitor status
input tag name field and enter a tag name.
For this example, Gas_Main is entered.
4. Right-click the tag name just entered and choose New
‘
tag_name’ from the list.
5. Click OK to accept the default setup for the new
PowerMonitor status input tag.
The PowerMonitor status input Add-on Instructions
also use explicit messaging to retrieve data from the
PowerMonitor devices. You must configure an explicit
message for each PowerMonitor status input. The table
lists the data and corresponding Add-On Instruction
parameters, tags, and addresses to be configured for each
status input.