Configure the Date and Time
Follow these steps to configure the date and time for the PowerMonitor 1000 device. The
Date and Time Setup Parameters
table on
page 66
shows the date and time parameters, and example settings
1.
Choose Configure Options>Date and
Time to access the Date and Time
Configuration page.
2.
Enter the default password of 0 or another valid
password to access Edit mode.
3.
Configure the date and time parameters accordingly.
4.
Click Submit to send the parameter changes to the
PowerMonitor 1000 device.
TIP
The password appears as asterisks (*).
If you don’t know the password, call
Rockwell Automation technical
support for assistance.
Date and Time Setup Parameters
Parameter
Range
Default
Example Settings
Password
0…9999
0
0
Date: Year
2001…2100
2005
Date:Month
1…12
1
Date:Day
1…31
0
Time:Hour
0…23
0
Time:Minute
0…59
0
Time:Seconds
0…59
0
Time:Hundreths
0…59
0