Chapter 3 Energy Data Collector Configuration
7.
Double-click the Dest tag assignment in the
MOV instruction and reassign the Dest tag to a
unique
ControllerName_EnergyTotals array
element in the CompactLogix tab of the
Energy Data worksheet.
This example shows the instruction used to
move Boiler_House_Gas.Val_Total_Gas to the
L2x_EnergyTotals file element [0].
8.
Repeat steps 2, 3, and 7 to program MOV instructions for the remaining Add-On Instruction total energy tags
(
AOIName.Val_Total_xxx.)
9.
Choose Map PLC/SLC Messages from the Logic
menu.
10.
In the PLC/SLC Mapping
dialog box:
a. Enter a PLC/SLC file number.
For this example, the PLC-5 file
number 10 is entered.
b. Choose the
ControllerName_EnergyTotals tag
from the Name list.
For this example, L2x_EnergyTotals is
selected.
c. Click OK.
This example shows the
L2x_EnergyTotals 4-element, tag array
mapped to the F10 PLC/SLC file.
TIP
FactoryTalk EnergyMetrix software meter tags reference these mapped tags by their PLC-5
equivalent addresses F10:0 through F10:3