Rockwell Automation Publication IASIMP-QS016C-EN-P - October 2014

439

Appendix

D

Digital and Analog Energy Add-On Instructions

This appendix describes the behavior of all Digital and Analog Energy Add-On Instructions with the exception of the
Energy_Electric_Analog or Energy_Electric Digital Add-On Instructions, described in Appendix C.

The Digital and Analog Energy Add-On Instructions perform four functions.

A total consumption calculation for the metered input. This value is stored in the output, Val_Total_xxx.
A consumption rate calculation for the metered input over a predefined interval set by the user. This value, also

known as Average Flow rate, is stored in the output, Val_

xxx_Per_Calc_Interval.

Equipment Status Faceplate update of the energy total Val_Total_xxx, the flow rate (Val_xxx_Per_Min or

Val_

xxx_Per_Hr), and energy device status information.

Alarm History Faceplate update of information needed to display predefined alarm messages based on the energy

device status.

CompactLogix Digital Input Logic

Logic is provided in all Energy_

xxx_Digital Add-On Instructions to calculate energy consumption from CompactLogix

digital inputs. The Inp_Pulse tag initiates an energy computation, where 1 pulse = 1 (unit).

Every time a pulse is triggered, the logic adds the value of the Set_Meter_Pulse_Factor tag to the Val_Total_

xxx (total

consumption) tag. The Set_Meter_Pulse_Factor, is set by default to 1, but can be user-defined for scaling purposes.

Energy Add-On Instruction

Unit

Air_Flow

cf

Fuel_Oil

gallons

Propane

gallons

Steam_Flow

lbs

Water_Flow

gallons