Rockwell Automation Publication IASIMP-QS016C-EN-P - October 2014

171

FactoryTalk EnergyMetrix Software Alarm Setup Chapter 8

Configure SMTP Server

You may need to make changes to the system configuration, for example, to set up an email SMTP server for alarm and
report emailing. You must have the Edit System Config privilege, an Admin privilege, to edit the system configuration.

For details on other system configuration parameters, refer to the FactoryTalk EnergyMetrix software online help.

Follow these steps to configure the SMTP server for emailing alarms or reports.

1.

Select Configuration on
the System tab.

2.

Under Email SMTP Server
Configuration, edit the
parameters as appropriate.

3.

Click Save.

Parameter

Description

Email Server Name or IP Address

Simple Mail Transport Protocol server name or IP

address. Contact your IT department for the correct

information.

Sender Email Address

Does not have to be a real email address.

Send Test Email To

Sends a test message to the email address entered in

the address field when the Send button is clicked.