FactoryTalk View ME Energy Faceplates
Chapter 11
14. Click the Communication tab on
the Message Configuration
dialog.
a. Click the Browse icon.
b. Select the path to the
PowerMonitor device.
For this example, select ETHERNET-MODULE Electric_Main_PM3000.
c. Click OK.
d. Verify the path is okay.
e. Verify CIP is the Communication Method.
f. Click OK to close the Message Configuration dialog box.
15. Assign the Val_Total_Real_Power parameter to the
associated controller-scoped tag.
a. Double-click the tag name field next to
Val_Total_Real_Power.
b. Click the pull-down menu icon then double-click
the associated controller-scoped tag to select it.
For this example, the tag is
Electric_Main_TotalRealPower.
16. Repeat steps 6…15 to configure the
remaining three PowerMonitor data
messages and tags.
Refer to the
PowerMonitor Add-On
Instruction Tag References
table on
page 321
for associated parameters, tags,
and addresses.
For this example, the completed
PM_3000 Add-On Instruction instance
for the Electric_Main meter looks like
this.
17. Repeat steps 1…16 for each
PowerMonitor 1000 or 3000 device in
your system.