Rockwell Automation Publication IASIMP-QS016C-EN-P - October 2014
363
Demand Control Chapter 12
Create or Open a Project in RSLogix 5000 Software
Follow these steps to create or open a project in RSLogix 5000 software.
1.
Open RSLogix 5000 software by clicking Start> Programs> Rockwell
Software> RSLogix 5000 Enterprise Series> RSLogix 5000.
The Quick Start window displays in the RSLogix workspace.
2.
Click Open Project to open an existing project, or click New Project.
3.
If you are creating a new project, configure the controller.
a. Choose your controller and revision number.
b. Enter a unique controller name.
c. Click OK.
Configure the PowerMonitor Unit
Follow these steps to configure a PowerMonitor unit.
1.
Right-click the Ethernet Port and choose New Module.
2.
Select ETHERNET-MODULE (Generic Ethernet Module) as the module
type and click OK.
3.
Configure the PowerMonitor's IP address and Connection Parameters and
then click OK.
PowerMonitor 1000/3000 Connection Parameters
Assembly Instance
Size
Input
1
16
Output
2
Configuration
3
0
PowerMonitor 5000 Connection Parameters
Assembly Instance
Size
Input
100
60
Output
101
1
Configuration
102
160