Rockwell Automation Energy Management Accelerator Toolkit Quick Start User Manual
Page 230

230
Rockwell Automation Publication IASIMP-QS016C-EN-P - October 2014
Chapter 11
FactoryTalk View ME Energy Faceplates
Configure RSLogix5000 for the PowerMonitor 500 Unit Faceplate
Follow these procedures to configure the faceplate.
Add the PowerMonitor 500 Unit to your Ethernet Network
1. Create a new or open an existing RSLogix5000 software (or Studio 5000 Logix Designer application) file.
2. Under I/O Configuration, right-click the network communication module to be used for the intended unit.
3. Select ‘New Module’.
4. From the Communication pull-down menu, choose ETHERNETMODULE Generic Ethernet Module.
5. Enter a distinct module name and the IP Address of your power monitor.
(For example, we use 'MyPM500' for the module name throughout this document.)
6. Enter the Connection Parameters as listed in this dialog box.
7. Click OK.
IMPORTANT
This step assumes you have already added and configured an Ethernet module to your I/O tree.