Rockwell Automation Energy Management Accelerator Toolkit Quick Start User Manual
Page 378

378
Rockwell Automation Publication IASIMP-QS016C-EN-P - October 2014
Chapter 12 Demand Control
2.
Enter your configured password.
3.
Configure the demand control schedule, kW setpoint,
and billing end date.
For the Efficient Industries example, the demand control
is on from 8:00 to 18:00, Monday through Friday.
4.
Click on the load config button to configure the
individual loads.
For the efficient industries example, loads are configured
as follows:
Load
Description
Priority
Rated KW
On Delay SEC
Off Delay SEC
Max Off Time
SEC
1
Air Compressor 1
1
21
60
60
900
2
Air Compressor 2
1
21
60
60
900
3
AHU 1 Production
4
15
120
120
1800
4
AHU 2 Production
4
15
120
120
1800
5
AHU 3 Shipping
5
12
120
120
1800
6
AHU 4 Office
7
10
120
120
1800
7
Exhaust Fan 1
2
2
30
30
2700
8
Exhaust Fan 2
2
2
30
30
2700
9
Exhaust Fan 3
10
2
30
30
2700
10
Exhaust Fan 4
10
2
30
30
2700
11
Lighting Production 3
6
15
15
1200
12
Lighting Production 6
6
15
15
1200
13
Lighting Shipping
8
6
15
15
3600
14
Lighting Office
9
6
15
15
3600