Rockwell Automation Energy Management Accelerator Toolkit Quick Start User Manual
Page 318

318
Rockwell Automation Publication IASIMP-QS016C-EN-P - October 2014
Chapter 11
FactoryTalk View ME Energy Faceplates
6. Enter a module name for the first
PowerMonitor device.
For this example, you will configure the first
PowerMonitor device named
Electric_Main_PM3000.
7. Choose Input Data-REAL from the Comm
Format list.
8. Enter Connection Parameters.
9. Enter the IP address of the PowerMonitor device.
For this example, the Electric_Main_PM3000 IP address is 10.10.10.0.
10. Click OK.
11. Repeat steps 1…9 to configure each PowerMonitor 1000 and 3000 device in your project.
, enter the names and IP addresses of the PowerMonitor devices in the table. The
rest of the parameters in the New Module dialog box are the same.
When done, the I/O configuration should look like this.
Table 2 - PowerMonitor 1000/3000 Connection Parameters
Assembly Instance
Size
Input
1
16
Output
2
Configuration
3
0
PowerMonitor Device Name
IP Address
Electric_Main_PM3000
10.10.10.0
Boiler_House_PM1000
10.10.10.1
Power_House_PM1000
10.10.10.2
Production1_PM1000
10.10.10.3
Production2_PM1000
10.10.10.4
Shipping_Receiving_DC_PM1000
10.10.10.5
MCC2_PM1000
10.10.10.6