Chapter 12 Create a PanelView Plus Application

Serial Shortcut

1. Right-click RSLinx

Enterprise and select Add
Driver.

2. Select Serial DF1 and

click OK.

3. Select the Comm Port on

your computer to which
you connected the
1756-CP3 cable.

4. In the Devices field,

select Logix Platform.

5. Check the Use

Auto-Configuration
check box and click OK.

IMPORTANT

Before you add the serial drive in this procedure, you must stop and delete the serial driver in RSLinx Classic
software. Depending on the messages that appear, you might have to take all programming and configuration
software offline and completely shutdown RSLinx Classic software.