Chapter 4 Prepare the PowerFlex 70 Drive
3. Remove a knockout from
the bottom plate on the
drive for routing the
power line conductors.
4. Wire the PowerFlex 70
240V AC, 3-phase line
power terminals to the
240V AC, 3-phase Load
connector on the line
interface module.
Fuse according to
PowerFlex power rating.
5. Wire the PE Chassis
ground terminal on the
PowerFlex 70 to earth
ground.
6. Connect the 240V
3-phase motor to the
PowerFlex T1, T2, T3,
PE terminals.
L1
R
L2
S
L3
T
BR1
+DC
BR2
BRK
T1
U
T2
V
T3
W
PE
PE
Optional LIM 240V AC
3-Phase Load Connector
Motor
fuse
fuse
fuse
Top View