3. Double-click a request from

one of the devices.

4. Enter a unique IP address for

each device.

5. Click OK.

If you are not on an isolated
network, obtain the IP
addresses from your network
administrator.

6. Repeat steps

3…5

for each

device, except for the
PanelView Plus terminal.

7. Select the first device in the Relation

List field.

8. Click Disable BOOTP/DHCP.

9. Repeat steps

7…8

for all devices

except for the PanelView Plus
terminal.

10. Close the BOOTP/DHCP utility.

If prompted to save changes, click No.

IMPORTANT

If you cycle power, the device will not retain its IP address unless you disable BOOTP/DHCP.