Chapter 3

ArmorStart DeviceNet Configuration

3. From the Monitor Tags tab, locate and

expand the ArmorStart 284D output tags.
Follow this procedure if you need to
change the value of a tag in RSLogix
software.

a. Select the tag value.

b. Enter or select the desire value.

c. Press Enter.

4. Change the FaultReset tag to 1 and press Enter to clear any initial faults.

5. Change FaultReset back to 0 and press enter.

6. Verify that the I.Status_ready tag value is 1, indicating that the device is ready.

7. Change the O.CommandFreq tag to 600 engineering units and press Enter.

This is 60.0 Hz.

8. Change the RunFwd tag to 1 and press Enter.

The display on the device registers the speed increase in Hz until the value entered at the reference tag is
reached.

9. Change the RunFwd tag back to 0.

The display on the ArmorStart device will show the speed decreasing until it reaches 0.00 Hz.

By starting and stopping the device, you verified that the:

• Logix controller is communicating correctly with the device.
• ArmorStart device can receive simple commands.

ATTENTION

If there is a motor attached to your device, completing the next step will cause it to turn.