Appendix B

Configure Design (local) Communication

The local tab in Communication Setup reflects the view of the topology from the RSLinx Enterprise server
on the development computer. For this example, the development computer is communicating with the L63
ControlLogix controller via Ethernet network.

Follow these steps to setup the Design Time path.

1. Expand Ethernet, Ethernet.

2. Expand the Ethernet bridge

assigned to you.

3. Expand CompactLogix System.

4. Select 0, 1756-L63.

5. Click Add.

A new device shortcut appears.

6. Name the shortcut CLX-L63.

7. Select the L63 shortcut and the

controller.

8. Click Apply.

A verification dialog box appears
showing that the shortcut was
assigned to the design path.

9. Close the verification dialog box.

The Apply button is dimmed indicating the shortcut is attached to the path.