Error Code

Message Information

Action

1.

Remove and reinstall the power supply.

2.

Check cables and subsystem components in the system

for damage.

3.

If the issue persists, see

Getting Help

.

PSU0031

Message

Cannot communicate with power supply <number>.

LCD Message

Cannot communicate with PSU <number>. Re-seat PSU.

Details

The power supply may operate, however power supply
monitoring will be degraded. System performance may be
degraded.

Action

Remove and reinstall the power supply. If the issue persists,
see

Getting Help

.

PSU1201

Message

Power supply redundancy is lost.

Details

The power supply will try to operate in a degraded state.
System Performance and power redundancy may be
degraded or lost.

Action

Check input power. Reinstall the power supply. If the issue
persists, see

Getting Help

.

PSU1202

Message

Power supply redundancy is degraded.

Details

The power supply will try to operate in a degraded state.
System Performance and power redundancy may be
degraded or lost.

Action

Remove input power and reinstall supply at the next service
window.

PSU1203

Message

The power supplies are not redundant.

LCD Message

Lost PSU redundancy. Check PSU cables.

Details

The current power operational mode is non-redundant
because of a power supply exception, a power supply
inventory change, or a system power inventory change.

Action

Check the event log for power supply failures. Review
system configuration and power consumption.

PSU1204

Message

The power supplies are not redundant. Insufficient resources
to maintain normal operations.