3 alarm relays – EVCO c-pro mega RACK User Manual

Page 104

Advertising
background image

C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL

Page

104

ACC1

C1 common oil differential

Settable

Display

Configurable delay

AFC1

C1 common fan thermal

Manual

Display

AL32

C2 supply pressure high

Auto

All fans ON

AL37

C2 suction pressure high

Auto

All comp. ON

Configurable delay

AL42

C2 supply pressure low

Auto

All fans OFF

- Configurable delay
- Only present if the
circuit is on

AL47

C2 suction pressure low

Auto

All comp. OFF

- Configurable delay
- Only present if the
circuit is on

AL12

C2 supply high pressure pressure-switch

Settable

All comp. OFF

AL22

C2 suction low pressure pressure-switch

Auto

All comp. OFF

Only present if the

circuit is on

AL62

C2 fluid level

Manual

Display

Configurable delay

ACC2

C2 common oil differential

Settable

Display

AFC2

C2 common fan thermal

Manual

Display

AL33

C3 supply pressure high

Auto

All fans ON

AL38

C3 suction pressure high

Auto

All comp. ON

Configurable delay

AL43

C3 supply pressure low

Auto

All fans OFF

- Configurable delay
- Only present if the
circuit is on

AL48

C3 suction pressure low

Auto

All comp. OFF

- Configurable delay
- Only present if the
circuit is on

AL13

C3 supply high pressure pressure-switch

Settable

All comp. OFF

AL23

C3 suction low pressure pressure-switch

Auto

All comp. OFF

Only present if the

circuit is on

AL63

C3 fluid level

Manual

Display

Configurable delay

ACC3

C3 common oil differential

Settable

Display

Configurable delay

AFC3

C3 common fan thermal

Manual

Display

ES07

Faulty or disconnected environment probe

Auto

Display

ES08

Faulty or disconnected external probe

Auto

Floating condensation
OFF

AH01

Hardware configuration error

Auto

Display

Appears when the
wizard attempts to
set a hardware
configuration not
attainable with the
available hardware
resources


(

*

¹) To reset alarms due to compressor/fan operating times it is necessary to zero the operating time

for the relevant device from the service menu. Once the times have been zeroed, the alarms relating
to the compressors/fans will be reset automatically.


7.3

Alarm relays


The program has the capacity to manage up to four alarm relays. Each alarm is enabled depending
on whether or not the relevant parameter, Alarm DO position, has been set. To enable, simply set
this to a value other than zero, if the value remains at zero, the alarm relay is not used.
The four relays, with relevant parameters, are listed below:

General alarm relay - Global alarm DO position

Circuit 1 alarm relay - Circuit 1 alarm DO position

Circuit 2 alarm relay - Circuit 2 alarm DO position

Circuit 3 alarm relay - Circuit 3 alarm DO position