C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL

Page

18


JMP3

CAN terminator

Jumper not inserted

Termination (120

?

) not inserted

Jumper inserted

Termination (120

?

) inserted

JMP4

Local CAN serial port baud rate selection

A

B

Jumper A inserted
Jumper B inserted


Baud rate = 20K

A

B

Jumper A inserted
Jumper B not inserted


Baud rate = 50K

A

B

Jumper A not inserted
Jumper B inserted


Baud rate = 125K

A

B

Jumper A not inserted
Jumper B not inserted


Baud rate = 500K

JMP5

RS-485 terminator

Jumper not inserted

Termination (120

?

) not inserted

Jumper inserted

Termination (120

?

) inserted

JMP6

Analogue output selection

A

B

C

D

Jumper A inserted
Jumper B inserted
Jumper C inserted
Jumper D inserted

Output AO1 under current
Output AO2 under current
Output AO3 under current
Output AO4 under current

A

B

C

D

Jumper A not inserted
Jumper B not inserted
Jumper C not inserted
Jumper D not inserted

Output AO1 under tension
Output AO2 under tension
Output AO3 under tension
Output AO4 under tension


PLEASE NOTE:

It is not sufficient to merely set the jumper to configure the signal distributed by the analogue
output, the controller machine parameters must also be set (see the chapter “Configuration of the
signal distributed by the analogue output” in the Hardware Manual).