EVCO c-pro mega RACK User Manual

Page 74

Advertising
background image

C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL

Page

74

The range of values the inverter output may assume is comprised of between 0 and 100 percentage
points, with two decimal places.
By enabling the inverter, for a given number of compressors, one step is lost, which will be replaced
by regulation with inverter on the first compressor.
Below is given an example of how to change regulation with the presence of an inverter.


6.3.4

Neutral zone regulation with inverter


This type of control introduces inverter control to normal neutral zone control, and in order to do
this it is essential to set several parameters relating to the inverter device it is intended to use, in
addition to enabling its use. The parameters in question are the following:

Inverter enabling

Minimum inverter value (MinI)

Inverter time (IT)

SpeedUp time

neutral zone suction setPoint











Regulation varies according to the zone (neutral, on or off) in which the regulator is located.

SP

SP + BP

Steps

Max Steps

Pressure

Pressure

SP + OFSI

SP + OFSI + DI

Inverter

MinI

100.00 %

SP

SP + BP

Steps

Max Steps

Pressure

Example: 4 compressors w/o inverter

Example: 4 compressors with 1 inverter