C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL

Page

68

6

REGULATIONS

6.1

Machine configuration


A Wizard (System builder menu) allows assisted configuration of the machine. The first choice
refers to the number of circuits (1, 2 or 3) by means of parameter PG01; in the case of dual and
triple circuit machines, the selection of the type of condensation, single or separate, (PG30) and the
presence, or otherwise, of an expansion unit (PG02) are also important. These 3 parameters define
the type of machine and the hardware supported, in accordance with the following table:

Machine type

Single-circuit

Dual-circuit

Triple-circuit

Single
condensation

n.r.

NO

YES

NO

YES

Probe AI 1

Suction pressure*

³

C1 suction

pressure*

³

C1 suction

pressure*

³

C1 suction

pressure*

³

C1 suction

pressure*

³

Probe AI 2

Supply pressure*

³

C1 supply

pressure*

³

Supply pressure*

³

C1 supply

pressure*

³

Supply pressure*

³

Probe AI 3

-

C2 suction

pressure*

³

C2 suction

pressure*

³

C2 suction

pressure*

³

C2 suction

pressure*

³

Probe AI 4

-

C2 supply

pressure*

³

-

C2 supply

pressure*

³

-

Probe AI 5

-

-

C3 suction

pressure*

³

C3 suction

pressure*

³

C3 suction

pressure*

³

Probe AI 6

-

-

-

C3 supply

pressure*

³

-

Probe AI 7

Environment

temperature

Environment

temperature

Environment

temperature

Environment

temperature

Environment

temperature

Probe AI 8

External

temperature

External

temperature

External

temperature

External

temperature

External

temperature

Analogue
output AO 1

Compressor with

inverter

Compressor with

inverter C1

Compressor with

inverter C1

Compressor /

Fan with inverter

C1 *

²

Compressor /

Fan with inverter

C1 *

²

Analogue
output AO 2

-

Compressor with

inverter C2

Compressor with

inverter C2

Compressor /

Fan with inverter

C2 *

²

Compressor with

inverter C2 *

²

Analogue
output AO 3

Fan with inverter

Fan with

inverter C1

Fan with inverter

C1

Compressor / Fan

with inverter C3 *

²

Compressor with

inverter C3 *

²

Analogue
output AO 4

-

Fan with inverter

C2

-

-

Fan with inverter

Number of
digital inputs

12 (22)*

¹

12 (22)*

¹

12 (22)*

¹

12 (22)*

¹

12 (22)*

¹

Number of
digital outputs

13 (26)*

¹

13 (26)*

¹

13 (26)*

¹

13 (26)*

¹

13 (26)*

¹

(

*

¹) If there is an expansion unit, the number of digital inputs and outputs increases, and it is

possible
to configure more hardware, depending on requirements.

(

*

²) In triple-circuit machines, inverter use is exclusively between compressors and fans.


(

*

³) The probes can also measure temperature by changing the relevant driver parameters: PH43,

PH44, PH45, PH47. Temperature is transformed into pressure by selecting the type of refrigerant
gas used (parameter PH31).