C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL

Page

51

PH36

Suction load
compensation
offset

Load loss compensation
factor

0.2

0.1

5.0

Bar

IS-V

PH40

Measurement
unit

Sets the display for
temperature or pressure
0: Pressure
1: Temperature

0

(Pres.)

0

(Pres.)

1

(Temp.)

IS-V

PH43

AI1 probe type

Sets the type of AI01
analogue input:
2: NTC
3: 0-20mA
4: 4-20mA

4

4-20mA

2

4

IS-V

PH44

AI2 probe type

Sets the type of AI02
analogue input:
2: NTC
3: 0-20mA
4: 4-20mA

4

4-20mA

2

4

IS-V

PH45

AI3_4 probe
type

Sets analogue input type for
AI03 and AI04:
2: NTC
3: 0-20mA
4: 4-20mA

4

4-20mA

2

4

IS-V

Visible if
PG01 > 1

PH47

AI5_6 probe
type

Sets analogue input type for
AI05 and AI06:
2: NTC
3: 0-20mA
4: 4-20mA

4

4-20mA

2

4

IS-V

Visible if
PG01 > 2

PH53

Buzzer enable

Enables the buzzer to sound

YES (1)

NO (0)

YES (1)

IS-V

PSd3

Installer PSd

Installer level password

0

-999

9999

IS-V

ALARM PARAMETERS

PH17

DI alarm logic

Sets the digital input alarm
logic used for controlling
the alarms:
0: Normally open NO
1: Normally closed NC

NC

NO (0)

NC (1)

IS-S

PH18

DO alarm logic

Sets the logic for the relays
used for the alarms
0: Normally open NO
1: Normally closed NC

NO

NO (0)

NC (1)

IS-S

PH19

Other DI logic

Sets the digital input alarm
logic used for controlling
the following functions:
- Global remote OnOff
- Circuit remote OnOff
- compressor/fan secondary
setpoint
0: Normally open NO
1: Normally closed NC

NO

NO (0)

NC (1)

IS-S