* VDC=12.5 V Imax = 200 mA (as the sum of the current values for all VDC terminals).

Card with 24 V AC/DC power supply

Conn.

Abbre

v.

Description

CA-1

VCC

card power supply input (24 VAC/DC)

CA-2

VCC

card power supply input (24 VAC/DC)

Other connectors (not present on the C-PRO EXP MEGA expansion unit)

Conn.

Abbre

v.

Description

JN-1

NC 9

relay No. 9 contact normally closed

JN-2

COM 9

relay No. 9 common connection

JN-3

NO 9

relay No. 9 contact normally open

JO-1

NC 10

relay No. 10 contact normally closed

JO-2

COM10

relay No. 10 common connection

JO-3

NO 10

relay No. 10 contact normally open

JP-1

COM11

relay No. 11 common connection

JP-2

NO 11

relay No. 11 contact normally open

JP-3

COM12

relay No. 12 common connection

JP-4

NO 12

relay No. 12 contact normally open

JP-5

COM13

relay No. 13 common connection

JP-6

NO 13

relay No. 13 contact normally open

JQ-1

DI9

No. 9 digital input 230 VAC

JQ-2

DI10

No. 10 digital input 230 VAC

JQ-3

CONHV

digital input common connection 230 VAC

Jumper and LED meanings

JMP3

CAN terminator

Jumper not inserted

Termination (120

?

) not inserted

Jumper inserted

Termination (120

?

) inserted

JMP4

Local CAN serial port baud rate selection

A

B

Jumper A inserted
Jumper B inserted


Baud rate = 20K

A

B

Jumper A inserted
Jumper B not inserted


Baud rate = 50K

A

B

Jumper A not inserted
Jumper B inserted


Baud rate = 125K

A

B

Jumper A not inserted
Jumper B not inserted


Baud rate = 500K


PLEASE NOTE:

The C-PRO MEGA RACK and the C-PRO GIGA RACK are configured by default to be able to
work with an expansion unit (with standard configuration) and with a user interface (with standard