8list of modbus variables – EVCO c-pro mega RACK User Manual

Page 106

Advertising
background image

C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL

Page

106

8

LIST OF MODBUS VARIABLES


It is possible to control the application by means of a supervisor module, using the Modbus
protocol. Communication uses an RS485 serial interface, already built in to the controller.
The various parameters exported by the application are reported below

8.1.1

Modbus export table (C-PRO GIGA)

REGISTER VARS LIST

id

Name

Value

Min

Max

Description

Mode

257

PackedDI1_16

0

0

65535

Bit1=DI01, Bit2=DI02 ... ,
Bit16=DI16

R/W

258

PackedDI17_22

0

0

65535

Bit1=DI17, Bit2=DI18, ...
Bit6=DI22

R/W

385

PackedDO1_16

0

0

65535

Bit1=DO01, Bit2=DO02,
... , Bit16=DO16

R/W

386

PackedDO17_26

0

0

65535

Bit1=DO17, Bit2=DO18,
... , Bit10=DO26

R/W

513

AI01_Pressure_SuctionC1

-

-

-

R/W

514

AI02_Pressure_SupplyC1

-

-

-

R/W

515

AI03_Pressure_SuctionC2

-

-

-

R/W

516

AI04_Pressure_SupplyC2

-

-

-

R/W

517

AI05_Pressure_SuctionC3

-

-

-

R/W

518

AI06_Pressure_SupplyC3

-

-

-

R/W

519

AI07_EnvironmentProbe

-

-

-

R/W

520

AI08_ExternalProbe

-

-

-

R/W

641

AO01_Inv_Circuit1

-

0.00

100.00

R/O

642

AO2_Inv_Circuit2

-

0.00

100.00

R/O

643

AO3_Inv_Circuit3

-

0.00

100.00

R/O

644

AO4_FanInv_OnUniqueCond

-

0.00

100.00

R/O

769

PackedAlarmW1

0

0

65535

Bit1=ES01, Bit2=ES02,
Bit3=ES03, Bit4=ES04,
Bit7=ES07, Bit8=ES08,
Bit15=ERTC, Bit16=EN01

R/W

770

PackedAlarmW2

0

0

65535

Bit1=AF21, Bit2=AF22,
Bit3=AF23, Bit4=AF24,
Bit5=AF25, Bit6=AF26,
Bit7=AF27, Bit8=AF28,
Bit9=AF29, Bit10=AF30,
Bit11=AF31, Bit12=AF32

R/W

771

PackedAlarmW3

0

0

65535

Bit1=AC21, Bit2=AC22,
Bit3=AC23, Bit4=AC24,
Bit5=AC25, Bit6=AC26,
Bit7=AC27, Bit8=AC28,
Bit9=AC29, Bit10=AC30,
Bit11=AC31, Bit12=AC32

R/W

Advertising