EVCO c-pro mega RACK User Manual

Page 47

Advertising
background image

C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL

Page

47

PF64

Fan inverter
minimum

Circuit 3

Differential for fan
regulation with circuit 3
inverter

0.5

0.0

20.0

Bar

IS-RF

Visible if PG01
> 2 and PG30 =
0 and
PG52 = 1

PF65

Fan inverter SP
offset.
Circuit 3

Suction setpoint offset for
circuit 3 inverter regulation
of the fan.

0.0

-20.0

20.0

Bar

IS-RF

Visible if PG01
> 2 and PG30 =
0 and
PG52 = 1

PF66

Fan inverter
minimum

Circuit 3

Minimum fan value with
circuit 3 inverter

0.0

0.0

100.0

%

IS-RF

Visible if PG01
> 2 and PG30 =
0 and
PG52 = 1

PF67

Fan inverter
speedup
Circuit 3

Fan speedup time with
circuit 3 inverter

2

0

999

Sec

IS-RF

Visible if PG01
> 2 and PG30 =
0 and
PG52 = 1

PF68

Fan inverter time
Circuit 3

Inverter ramp. Time taken
for the inverter to go from
the minimum value to the
maximum value ( circuit 3
neutral zone reg.)

10

0

999

Sec

IS-RF

Visible if PG01
> 2 and PG30 =
0 and
PG52 = 1

PF01

Fan rotation

Type of rotation used for
fan management:
0: FIFO
1: LIFO
2: FIFO + time
3: LIFO + time

FIFO

FIFO (0)

LIFO

+ time

(3)

IS-F

PF02

Enable
compressor
regulation

If enabled, allows selection
of fan regulation, only if at
least one compressor is on

NO

NO (0)

YES (1)

IS-F

PF07

TOnOther

Minimum time that must
elapse before another fan
can be switched on

2

0

999

Sec

IS-F

PF08

TOffOther

Minimum time that must
elapse before another fan
can be switched off

2

0

999

Sec

IS-F

PF11

Fan probe error
Circuit 1

Number of fans that will be
forced if an alarm occurs on
the circuit 1 supply probe

1

0

PG41

IS-F

PF31

Fan probe error
Circuit 2

Number of fans that will be
forced if an alarm occurs on
the circuit 2 supply probe

1

0

PG45

IS-F

Visible if PG01
> 1 and
PG30 = 0

PF51

Fan probe error
Circuit 3

Number of fans that will be
forced if an alarm occurs on
the circuit 3 supply probe

1

0

PG51

IS-F

Visible if PG01
> 2 and
PG30 = 0

PF71

Enable floating
condensation

Enables floating
condensation for fan
management

NO

NO (0)

YES (1)

IS-F