6.4.11

Refrigeration power incrementing at high pressures


In order to avoid tripping the condensation high pressure pressure-switch, with consequent blocking
of cold production, it is possible to reduce the refrigeration power and consequently the power to be
exchanged by the condenser, thus reducing condensation pressure. This reduction is only possible
with incrementable circuits (with at least two compressors or with one compressor with
incrementing devices).

The parameters pertaining to this function are as follows:

PC70 = Enable high pressure incrementing

PC71 = Condensation pressure-switch control setpoint limit (Circuit 1)

PC72 = Condensation pressure-switch control setpoint limit (Circuit 2)

PC73 = Condensation pressure-switch control setpoint limit (Circuit 3)

PC74 = Pressure-switch control differential

PC75 = Minimum pressure-switch increment maintenance time

PC76 = Percentage increment value


Supply
pressure

Set

Set-Diff

Increment
enabling

PC75

PC75

t

t