6.7

Miscellaneous controls

6.7.1

Inverter configuration (compressors/fans)


If selected, the inverter is always the first compressor in each circuit:

1 Circuit: the inverter (if enabled) is compressor 1

2 Circuits: the circuit 1 inverter (if enabled) is compressor 1, and the circuit 2 inverter (if
enabled) is the first compressor configured on the second circuit

3 Circuits: the circuit 1 inverter (if enabled) is compressor 1, the circuit 2 inverter (if
enabled) is the first compressor configured on the second circuit, and the circuit 3 inverter
(if enabled) is the first compressor configured on the third circuit


The inverter is included in the number of compressors or fans configured by parameter for
each circuit.

Example 1
1 Circuit
Compressor inverters YES
5 Compressors
0 Steps
Fan inverters NO
3 Fans

Example 2
1 Circuit
Compressor inverters NO
5 Compressors
2 Steps
Fan inverters NO
3 Fans


Example 1 configuration parameters:
CircuitNumber

1

Enable Circuit 1 Compressor Inverter YES
Number of Compressors for Circuit 1 6
Number of Compressor Steps

0

Enable Circuit 1 Fan Inverter

NO

Number of Fans for Circuit 1

3

Example 2 configuration parameters:
CircuitNumber

1

Enable Circuit 1 Compressor Inverter NO
Number of Compressors for Circuit 1 5
Number of Compressor Steps

2

Enable Circuit 1 Fan Inverter

NO

Number of Fans for Circuit 1

3


Depending on the single/dual/triple-circuit version, there are limitations on the use of inverters:

Single-circuit:

One compressor inverter (Analogue output 1)

One fan inverter (Analogue output 3)


Dual-circuit:

Two compressor inverters (Analogue outputs 1 - 2)

Two fan inverters (Analogue outputs 3 -4)


Triple-circuit:

Three compressor inverters (Analogue outputs 1 – 2 - 3) or

Three fan inverters (Analogue outputs 1 – 2 - 3)

Three compressor inverters (Analogue outputs 1 - 2 - 3) and one fan inverter (Analogue
output 4) in the case of unique condensation


In the case of the triple-circuit version, the inverters are exclusive: it is only possible to select those
pertaining to compressors, or those pertaining to fans. Management of a combination of both types