C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL

Page

72

The PC78 Sideband step overlap parameter allows improvements in the behaviour of this type of
regulation, which requires broad proportional bands in order to be stable, thus modifying the
subdivision of the regulation band between steps:

The insertion of steps occurs at PC78% of the proportional band, while release occurs at 100 –
PC78%
of the band; if for example PC78 = 60%, steps are inserted between 60% and the maximum
value (100%) of the proportional band PB, and in the same way released between 40% and the
minimum value (0%) of the same band PB.
It is obvious that by using step division, as indicated in the figure, the activity interval of each
individual step is greater with respect to standard geometric division, with the obvious advantage
that the proportional band may be reduced, in favour of greater regulation accuracy, and/or the
activation of the steps occurs with reduced frequency, or reduced compressor start-ups, to the
benefit of the mechanical lifespan of the same.

6.3.2

Neutral zone regulation


This type of regulation envisages the definition of a neutral zone, within which no activation or
deactivation decision will be taken, i.e. startup operations will not be requested for any of the
devices.
The parameters defining this regulation are as follows:

Neutral zone (NZ)

Out of zone differential (Diff)

Side band suction SetPoint (SP)

Outwith said neutral zone, device on or off requests for the various steps provided by the
compressors will follow this logic:

Switch on : When the suction pressure exceeds the setPoint + Neutral Zone threshold

Switch off : when the pressure drops below the setPoint

In this type of regulation, the neutral zone is displaced to the right of the setPoint.
As may be deduced from the figure, regulation envisages setting times, within which, depending on

100 - PC78 %

SP

SP + BP

Steps

Max Steps

Suction

PC78 %

Insertion

Release

SP

SP + ZN

SP + ZN + Diff

SP - Diff

NZ_TOnMin

NZ_TOnMax

NZ_TOffMax

NZ_TOffMin

Neutral zone

Switching on

Switching off

Suction pressure