EVCO c-pro mega RACK User Manual

Page 38

Advertising
background image

C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL

Page

38

PM21..30

Compressor
forcing
(1..10)

In manual operation, this
sets the number of forced
compressor steps

0

0

4

MA-M

Compressors 1
to 10; Visibility

PM33
PM34

Enable
compressor
(11-12)

Enables manual/automatic
operation of each
compressor:
M: manual

A: normal operation

A

A (0)

M (1)

MA-M

Compressors
11 and 12;
Visibility

PM35
PM36

Compressor
forcing
(11-12)

In manual operation, this
sets the number of forced
compressor steps

0

0

4

MA-M

Compressors
11 and 12;
Visibility

PM37

Comp. inverter
forcing Circuit 1

In manual operation, this
forces the compressor with
the circuit 1 inverter

0

0

100.0

%

MA-M

PM38

Comp. inverter
forcing Circuit 2

In manual operation, this
forces the compressor with
the circuit 2 inverter

0

0

100.0

%

MA-M

PM39

Comp. inverter
forcing Circuit 3

In manual operation, this
forces the compressor with
the circuit 3 inverter

0

0

100.0

%

MA-M

PM51..60

Enable
fan
(1..10)

Enables manual/automatic
operation of each fan:
M: manual

A: normal operation

A

A (0)

M (1)

MA-M

Fans 1 to 10;
Visibility

PM61..70

Fan forcing
(1..10)

In manual operation, this
forces the fans to be
switched on and off:
S: fan off

A: fan on

S

S (0)

A (1)

MA-M

Fans 1 to 10;
Visibility

PM73
PM74

Enable
fan
(11-12)

Enables manual/automatic
operation of each fan:
M: manual

A: normal operation

A

A (0)

M (1)

MA-M

Fans 11 and 12;
Visibility

PM75
PM76

Fan forcing
(11-12)

In manual operation, this
forces the fans to be
switched on and off:
S: fan off

A: fan on

S

S (0)

A (1)

MA-M

Fans 11 and 12;
Visibility

PM77

Circuit 1 inverter
fan forcing

In manual operation, this
forces the fan with the
circuit 1 inverter

0

0

100.0

%

MA-M

PM78

Circuit 2 inverter
fan forcing

In manual operation, this
forces the fan with the
circuit 2 inverter

0

0

100.0

%

MA-M

PM79

Circuit 3 inverter
fan forcing

In manual operation, this
forces the fan with the
circuit 3 inverter

0

0

100.0

%

MA-M

PM81

Suction probe 1
calibration

Circuit 1 suction probe
calibration

0.0

-9.9

9.9

Bar

MA-IO

PM82

Suction probe 2
calibration

Circuit 2 suction probe
calibration

0.0

-9.9

9.9

Bar

MA-IO

Visible if PG01
> 1

Advertising
This manual is related to the following products: