C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL

Page

41

Circuit 2

the minimum value to the
maximum value ( circuit 2
neutral zone reg.)

1

PC52

Compressor min.
setpoint
Circuit 3

Minimum suction setpoint
value pertaining to the
compressors of circuit 3

0.1

PH01

SPC3

Bar

IS-RC

Visible if PG01
> 2

PC53

Compressor
max. setpoint
Circuit 3

Maximum suction setpoint
value pertaining to the
compressors of circuit 3

2.5

SPC3

PH02

Bar

IS-RC

Visible if PG01
> 2

PC54

Compressor
regulation
Circuit 3

Sets the type of regulation
for controlling the circuit 3
compressors

Neutral

Zone (1)

Side

Band (0)

Neutral

Zone (1)

IS-RC

Visible if PG01
> 2

PC56

Compressor
integral time
Circuit 3

Integral time Ti for side
band regulation of circuit 3
compressors

600

0

999

Sec

IS-RC

Visible if PG01
> 2 and
PC54 = 0

PC57

Compressor
proportional
band. Circuit 3

Proportional band Bp for
side band regulation of
circuit 3 compressors

0.5

0

20.0

Bar

IS-RC

Visible if PG01
> 2 and
PC54 = 0

PC58

Comp. zone
Circuit 3

Zone value for neutral zone
regulation of circuit 3
compressors

0.5

0

20.0

Bar

IS-RC

Visible if PG01
> 2 and
PC54 = 1

PC59

Comp. zone
differential

Circuit 3

Differential, for neutral zone
regulation, within which the
calculation for the
insertion/release time of the
subsequent step varies.
Circuit 3

0.5

0

20.0

Bar

IS-RC

Visible if PG01
> 2 and
PC54 = 1