C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL

Page

37

PUF2

Fan secondary
setpoint offset
Circuit 2

Sets the offset value for use
of secondary setpoint from
fan digital input

0.0

-20.0

20.0

Bar

UT

Visible if PG01
> 1 and
PG30 = 0

PUF5

Fan sup.
secondary
setpoint offset
Circuit 2

Sets the offset value for use
of secondary setpoint from
fan supervisor

0.0

-20.0

20.0

Bar

UT

Visible if PG01
> 1 and
PG30 = 0

SPF3

Fan setpoint
Circuit 3

Sets the setpoint value for
the fan supply probe

15.0

PF52

PF53

Bar

UT

Visible if PG01
> 2 and
PG30 = 0

PUF3

Fan secondary
setpoint offset
Circuit 3

Sets the offset value for use
of secondary setpoint from
fan digital input

0.0

-20.0

20.0

Bar

UT

Visible if PG01
> 2 and
PG30 = 0

PUF6

Fan sup.
secondary
setpoint offset
Circuit 3

Sets the offset value for use
of secondary setpoint from
fan supervisor

0.0

-20.0

20.0

Bar

UT

Visible if PG01
> 2 and
PG30 = 0

PSd1

User PSd

User level password

0

-999

9999

UT

SERVICE MENU PARAMETERS

PM00

Compressor
operational time
alarm threshold

Sets the maximum
compressor operation time
limit. Beyond this limit, the
relevant alarm will be
tripped

20000

0

500000

Hou

rs

MA-F

PM01..10

Compressor
operation
time (1..10)

Operation times for each
compressor

0

0

500000

Hou

rs

MA-F

Compressors 1
to 10;
Visibility

PM31
PM32

Compressor
operation
time (11-12)

Operation times for each
compressor

0

0

500000

Hou

rs

MA-F

Compressors
11 and 12;
Visibility

PM40

Fan operational
time alarm
threshold

Sets the maximum fan
operation time limit.
Beyond this limit, the
relevant alarm will be
tripped

20000

0

500000

Hou

rs

MA-F

PM41..50

Fan operation
time (1..10)

Operation times for each fan

0

0

500000

Hou

rs

MA-F

Fans 1 to 10;
Visibility

PM71
PM72

Fan operation
time (11-12)

Operation times for each fan

0

0

500000

Hou

rs

MA-F

Fans 11 and 12;
Visibility

PM90

Last maintenance
date

Sets the last date on which
system maintenance was
carried out

MA-F

PSd2

Service PSd

Service level password

0

-999

9999

MA-F

PM11..20

Enable
compressor
(1..10)

Enables manual/automatic
operation of each
compressor:
M: manual

A: normal operation

A

A (0)

M (1)

MA-M

Compressors 1
to 10; Visibility