C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL

Page

39

PM83

Suction probe 3
calibration

Circuit 3 suction probe
calibration

0.0

-9.9

9.9

Bar

MA-IO

Visible if PG01
> 2

PM84

Supply probe 1
calibration

Circuit 1 supply probe
calibration

0.0

-9.9

9.9

Bar

MA-IO

PM85

Supply probe 2
calibration

Circuit 2 supply probe
calibration

0.0

-9.9

9.9

Bar

MA-IO

Visible if PG01
> 1 and PG30 =
0

PM86

Supply probe 3
calibration

Circuit 3 supply probe
calibration

0.0

-9.9

9.9

Bar

MA-IO

Visible if PG01
> 2 and PG30 =
0

PM87

Environment
temperature
probe calibration

Calibration of the
environment temperature
probe

0.0

-9.9

9.9

Bar

MA-IO

PM88

External
temperature
probe calibration

Calibration of the external
temperature probe

0.0

-9.9

9.9

Bar

MA-IO

INSTALLER MENU PARAMETERS

PC12

Compressor min.
setpoint
Circuit 1

Minimum suction setpoint
value pertaining to the
compressors of circuit 1

0.1

PH01

SPC1

Bar

IS-RC

PC13

Compressor
max. setpoint
Circuit 1

Maximum suction setpoint
value pertaining to the
compressors of circuit 1

2.5

SPC1

PH02

Bar

IS-RC

PC14

Compressor
regulation
Circuit 1

Sets the type of regulation
for controlling the circuit 1
compressors

Neutral

Zone (1)

Side

Band (0)

Neutral

Zone (1)

IS-RC

PC16

Compressor
integral time
Circuit 1

Integral time Ti for side
band regulation of circuit 1
compressors

600

0

999

Sec

IS-RC

Visible if PC14
= 0

PC17

Compressor
proportional
band. Circuit 1

Proportional band Bp for
side band regulation of
circuit 1 compressors

0.5

0

20.0

Bar

IS-RC

Visible if PC14
= 0

PC18

Comp. zone
Circuit 1

Zone value for neutral zone
regulation of circuit 1
compressors

0.5

0

20.0

Bar

IS-RC

Visible if PC14
= 1

PC19

Comp. zone
differential

Circuit 1

Differential, for neutral zone
regulation, within which the
calculation for the
insertion/release time of the
subsequent step varies.
Circuit 1

0.5

0

20.0

Bar

IS-RC

Visible if PC14
= 1

PC20

Compressor
TOnMin
Circuit 1

Minimum insertion time for
subsequent compressor step
( circuit 1 neutral zone reg.)

20

0

PC21

Sec

IS-RC

Visible if PC14
= 1

PC21

Compressor
TOnMax
Circuit 1

Maximum insertion time for
subsequent compressor step
( circuit 1 neutral zone reg.)

60

PC20

999

Sec

IS-RC

Visible if PC14
= 1

PC22

Compressor
TOffMin
Circuit 1

Minimum release time for
subsequent compressor step
( circuit 1 neutral zone reg.)

10

0

PC23

Sec

IS-RC

Visible if PC14
= 1

PC23

Compressor
TOffMax
Circuit 1

Maximum release time for
subsequent compressor step
( circuit 1 neutral zone reg.)

60

PC22

999

Sec

IS-RC

Visible if PC14
= 1

PC24

Comp. inverter
diff.

Circuit 1

Differential for compressor
regulation with circuit 1
inverter

0.5

0.0

20.0

Bar

IS-RC

Visible if PG12
= 1

PC25

Compressor
inverter SP

Suction setpoint offset for
circuit 1 inverter regulation

0.0

-20.0

20.0

Bar

IS-RC

Visible if PG12
= 1