C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL

Page

61

SYSTEM BUILDER MENU PARAMETERS – Other hardware digital input/output positions

Hd01

Global OnOff DI
position

Sets the position of the
system global on/off digital
input

0

0

12 (22)

CO-Hw

Max =10(18)
on C-PRO
MEGA RACK

Hd02

Comp. sec. setP
DI position

Sets the position for
compressor management
secondary setpoint digital
input

0

0

12 (22)

CO-Hw

Max =10(18)
on C-PRO
MEGA RACK

Hd03

Fan sec. setP DI
position

Sets the position for fan
management secondary
setpoint digital input

0

0

12 (22)

CO-Hw

Max =10(18)
on C-PRO
MEGA RACK

Hd11

C1 OnOff DI
position

Sets the position of the
circuit 1 on/off digital input

0

0

12 (22)

CO-Hw

Max =10(18)
on C-PRO
MEGA RACK

Hd12

C1 fluid level
alarm DI pos.

Sets the position of the
circuit 1 fluid level alarm
digital input

7

0

12 (22)

CO-Hw

Default = 6
Max =10(18)

on C-PRO
MEGA RACK

Hd13

C1 suction LP
alarm DI pos.

Sets the position of the
circuit 1 suction pressure-
switch low pressure alarm
digital input

9

0

12 (22)

CO-Hw

Default = 7
Max =10(18)

on C-PRO
MEGA RACK

Hd14

C1 supply HP
alarm DI pos.

Sets the position of the
circuit 1 supply pressure-
switch high pressure alarm
digital input

11

0

12 (22)

CO-Hw

Default = 8
Max =10(18)

on C-PRO
MEGA RACK

Hd15

C1 comp. oil
diff. alarm DI
pos.

Sets the position of the
circuit 1 compressor oil
differential alarm digital
input

0

0

12 (22)

CO-Hw

Max =10(18)
on C-PRO
MEGA RACK

Hd16

C1 comp. fan
thermal alarm DI
pos.

Sets the position of the
circuit 1 common fan
thermal alarm digital input

5

0

12 (22)

CO-Hw

Max =10(18)
on C-PRO
MEGA RACK

Hd21

C2 OnOff DI
position

Sets the position of the
circuit 2 on/off digital input

0

0

12 (22)

CO-Hw

Max =10(18)
on C-PRO
MEGA RACK;
Visible if PG01
> 1

Hd22

C2 fluid level
alarm DI pos.

Sets the position of the
circuit 2 fluid level alarm
digital input

8

0

12 (22)

CO-Hw

Default = 0
Max =10(18)

on C-PRO
MEGA RACK;
Visible if PG01
> 1

Hd23

C1 suction LP
alarm DI pos.

Sets the position of the
circuit 2 suction pressure-
switch low pressure alarm
digital input

10

0

12 (22)

CO-Hw

Default = 0
Max =10(18)

on C-PRO
MEGA RACK;
Visible if PG01
> 1