EVCO c-pro mega RACK User Manual

Page 16

Advertising
background image

C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL

Page

16

Conn.

Abbre

v.

Description

JK-3

COM 4 relay No. 4 common connection

JK-4

NO 4

relay No. 4 contact normally open

JK-5

COM 5 relay No. 5 common connection

JK-6

NO 5

relay No. 5 contact normally open

JL-1

COM 6 relay No. 6 common connection

JL-2

NO 6

relay No. 6 contact normally open

JL-3

COM 7 relay No. 7 common connection

JL-4

NO 7

relay No. 7 contact normally open

JL-5

COM 8 relay No. 8 common connection

JL-6

NO 8

relay No. 8 contact normally open

YB

PRG

not used

YC-1

RS485+

connector for connecting the RS485 serial port (RS485+)

YC-2

RS485-

connector for connecting the RS485 serial port (RS485-)

YC-3

GND

connector for connecting the RS485 serial port (ground)

JM-1

AO 1

No. 1 analogue output (0,5 .. 10 V / 0 .. 20 mA / 4 .. 20 mA)

JM-2

AO 2

No. 2 analogue output (0,5 .. 10 V / 0 .. 20 mA / 4 .. 20 mA)

JM-3

AO 3

No. 3 analogue output (0,5 .. 10 V / 0 .. 20 mA / 4 .. 20 mA)

JM-4

AO 4

No. 4 analogue output (0,5 .. 10 V / 0 .. 20 mA / 4 .. 20 mA)

JM-5

GND

analogue output common ground

C2-1

VCC*

serial port and optoisolated analogue output secondary power supply input (+15 VDC)

C2-2

GND*

secondary power supply reference

* VDC=12.5 V Imax=200 mA (as the sum of the current for all VDC terminals).

Card with 24 VAC/DC power supply

Conn.

Abbre

v.

Description

CA-1

VCC

main card power supply input (23 V AC/DC)

CA-2

VCC

main card power supply input (23 V AC/DC)

Warning:

With reference to the “Power supply” entries, the secondary power supply feeds the following
services:

the analogue outputs

the standard RS-485 port

the optional RS-485 port (or RS-232 port).

So that these services are optoisolated, the main power supply and the secondary power supply must
be galvanically isolated from one another.

If the controller is powered with 24 VAC/DC (i.e. by means of the connector hereinafter referred to
as CA), the following services will not be optoisolated:

the analogue outputs

the standard RS-485 port

the optional RS-485 port (or RS-232 port).