C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL

Page

52

PA01

Enable
compressor
operation time
alarm

Enables the alarm pertaining
to compressor operation
times

NO

NO (0)

YES (1)

IS-S

PA02

Enable fan
operation time
alarm

Enables the alarm pertaining
to fan operation times

NO

NO (0)

YES (1)

IS-S

PA03

HP suction alarm
delay

Sets the suction high
pressure alarm activation
delay

30

0

999

Sec

IS-S

PA04

ExPro alarm
delay

Sets the expansion unit
alarm activation delay

1

0

999

Sec

IS-S

Only in
versions with
expansion unit

PA05

Fluid level alarm
delay

Sets the fluid level alarm
activation delay

90

0

999

Sec

IS-S

PA06

Probe alarm
delay

Sets the suction and supply
alarm signalling delay

5

0

240

Sec

IS-S

PA07

Supply LP alarm
delay

Sets the supply low pressure
alarm activation delay

30

0

999

Sec

IS-S

PA08

LP suction alarm
delay

Sets the suction low
pressure alarm activation
delay

30

0

999

Sec

IS-S

PA09

Comp. thermal
alarm delay

Sets the compressor thermal
alarm activation delay

0

0

999

Sec

IS-S

PA10

Oil differential
alarm delay

Sets the common oil
differential and compressor
alarm activation delay

10

0

999

Sec

IS-S

PA11

Supply pressure
switch alarm
reset

Sets the type of reset for the
supply pressure-switch
alarm

M

A (0)

M (1)

IS-S

M:manual
A: automatic

PA12

Comp. thermal
alarm reset

Sets the compressor thermal
alarm reset type

M

A (0)

M (1)

IS-S

M: manual

A: automatic

PA13

Comp. pressure-
switch alarm
reset

Sets the compressor
pressure-switch alarm reset
type

M

A (0)

M (1)

IS-S

M: manual

A: automatic

PA14

Oil diff. alarm
reset

Sets the compressor oil
differential alarm reset type
.

M

A (0)

M (1)

IS-S

M: manual

A: automatic

PA23

Fan thermal
alarm reset

Sets the fan thermal alarm
reset type

M

A (0)

M (1)

IS-S

M: manual

A: automatic

PA15

C1 suction LP
alarm setpoint

Circuit 1 suction probe low
pressure alarm setpoint

0.5

PH01

PA17

Bar

IS-S

PA16

C1 suction LP
alarm diff.

Circuit 1 suction probe low
pressure alarm differential

0.5

0.0

20.0

Bar

IS-S

PA17

C1 suction HP
alarm setpoint

Circuit 1 suction probe high
pressure alarm setpoint

4.0

PA15

PH02

Bar

IS-S

PA18

C1 suction HP
alarm diff.

Circuit 1 suction probe high
pressure alarm differential

0.5

0.0

20.0

Bar

IS-S

PA19

C1 supply LP
alarm setpoint

Circuit 1 supply probe low
pressure alarm setpoint

2.0

PH03

PA21

Bar

IS-S

PA20

C1 supply LP
alarm diff.

Circuit 1 supply probe low
pressure alarm differential

0.5

0.0

20.0

Bar

IS-S

PA21

C1 supply HP
alarm setpoint

Circuit 1 supply probe high
pressure alarm setpoint

20.0

PA19

PH04

Bar

IS-S

PA22

C1 supply HP
alarm diff.

Circuit 1 supply probe high
pressure alarm differential

1.0

0.0

20.0

Bar

IS-S

PA25

C2 suction LP
alarm setpoint

Circuit 2 suction probe low
pressure alarm setpoint

0.5

PH01

PA27

Bar

IS-S

Visible if PG01
> 1

PA26

C2 suction LP

Circuit 2 suction probe low

0.5

0.0

20.0

Bar

IS-S

Visible if PG01