C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL

Page

33

The SYSTEM menu contains a system configuration “Wizard” for configuring a number of circuits,
activating unique condensation, the use of inverters, the number of compressors and increments, the
number of fans, the number of safety devices to be used and the use of any expansion units. A page
summarising the relays and selected digital inputs is presented for configuration purposes,
indicating whether an expansion unit should be used, if selected.

The HARDWARE menu contains all the parameters for setting the positions to which the various
devices are connected.

Compressor digital output position

Fan digital output position

Alarm digital input/output position


Such characteristics are collected in a separate submenu in order to distinguish compressors, fans
and safety devices.

Setting the positions of the various alarm inputs also enables their operation. Indeed, an alarm is
only enabled if the parameter, identifying its physical position on the terminal, is set and is other
than zero. If it is desired not to use an alarm, simply leave the corresponding parameter at the value
zero.
The same management is used to manage the four alarm relays. If the position parameters are equal
to zero, then the relays are disabled.

The PARAMETERS menu contains other machine configuration parameters:

type of control unit (only for viewing on the pages)

home page

passwords for all four levels


Firmware version

Keep pressed the UP+DOWN buttons for 2 seconds and enter in to the section info page.












Proj

(Project)

Firmware

No.

291

No.

1008

Version

4

Version

7

Release

0

Release

0