C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL

Page

54

PA39

C3 supply LP
alarm setpoint

Circuit 3 supply probe low
pressure alarm setpoint

2.0

PH03

PA41

Bar

IS-S

Visible if PG01
> 2 and PG30 =
0

PA40

C3 supply LP
alarm diff.

Circuit 3 supply probe low
pressure alarm differential

0.5

0.0

20.0

Bar

IS-S

Visible if PG01
> 2 and PG30 =
0

PA41

C3 supply HP
alarm setpoint

Circuit 3 supply probe high
pressure alarm setpoint

20.0

PA39

PH04

Bar

IS-S

Visible if PG01
> 2 and PG30 =
0

PA42

C3 supply HP
alarm diff.

Circuit 3 supply probe high
pressure alarm differential

1.0

0.0

20.0

Bar

IS-S

Visible if PG01
> 2 and PG30 =
0

PH16

Compressor
safety device
type

Sets the type of safety
devices used for the
compressors:
0: None
1: Thermal
2: Thermal + pressure-
switch
3: Thermal + oil diff.
4: All

Thermal

None (0)

All (4)

IS-S

SYSTEM BUILDER MENU PARAMETERS

PG01

Circuit number

Sets the number of circuits
for the machine

2

1

3

CO-W

Default = 1
on C-PRO
MEGA RACK

PG02

Enable
expansion

Enables the expansion unit
and the corresponding
alarms

NO

NO (0)

YES (1)

CO-W

PG03

Enable
differently
powered
compressors

Enables the management of
compressors with different
nominal power ratings

NO

NO (0)

YES (1)

CO-W

PG04

Number of
increments per
compressor

Sets the number of
increments for each
compressor

1

0

3

CO-W

Default = 0
on C-PRO
MEGA RACK

PG05

Number of safety
devices per
compressor

Sets the number of safety
devices for each compressor

1

0

3

CO-W

PG11

Number of
compressors for
Circuit 1

Sets the number of
compressors for circuit 1

2

0

12

CO-W

Default = 4
Max = 8
on C-PRO
MEGA RACK

PG12

Circuit 1 inverter
comp. enable

Enables the compressor
with circuit 1 inverter

NO

NO (0)

YES (0)

CO-W

PG15

Number of
compressors for
Circuit 2

Sets the number of
compressors for circuit 2

2

0

12

CO-W

Default = 0
Max = 8
on C-PRO
MEGA RACK;
Visible if PG01
> 1

PG16

Circuit 2 inverter
comp. enable

Enables the compressor
with circuit 2 inverter

NO

NO (0)

YES (0)

CO-W

Visible if PG01
> 1

PG21

Number of
compressors for
Circuit 3

Sets the number of
compressors for circuit 3

0

0

12

CO-W

Max = 8
on C-PRO
MEGA RACK;
Visible if PG01
> 2

Advertising