EVCO c-pro mega RACK User Manual

Page 23

Advertising
background image

C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL

Page

23

2.7.3

Input and output identification tables

Card with 12 VDC power supply

Conn.

Abbre

v.

Description

C1-1

VCC

card power supply input (+13 V DC)

C1-2

GND

power supply reference

JD-1

VDC

active probe power supply (*1)

JD-2

AI1

No.1 configurable analogue input (NTC, 0..20 mA, 4..20 mA)

JD-3

AI2

No.2 configurable analogue input (NTC, 0..20 mA, 4..20 mA)

JD-4

AI3

No.3 configurable analogue input (NTC, 0..20 mA, 4..20 mA)

JD-5

AI4

No.4 configurable analogue input (NTC, 0..20 mA, 4..20 mA)

JD-6

GND

analogue input common ground

JF-1

COM

digital input common connection

JF-2

DI1

No.1 digital input 12-24 VAC/DC

JF-3

DI2

No.2 digital input 12-24 VAC/DC

JF-4

DI3

No.3 digital input 12-24 VAC/DC

JF-5

DI4

No.4 digital input 12-24 VAC/DC

JF-6

COM

digital input common connection

JG-1

COM

digital input common connection

JG-2

DI5

No.5 digital input 12-24 VAC/DC

JG-3

DI6

No.6 digital input 12-24 VAC/DC

JG-4

DI7

No.7 digital input 12-24 VAC/DC

JG-5

DI8

No.8 digital input 12-24 VAC/DC

JG-6

COM

digital input common connection

YA-1

VDC

power supply output connector (12 VDC)

YA-2

CAN1+

connector for connecting the CAN serial port (CAN+)

YA-3

CAN1-

connector for connecting the CAN serial port (CAN-)

YA-4

GND

power supply output reference connector (ground)

JH-1

NC 1

relay No. 1 contact normally closed

JH-2

COM 1

relay No. 1 common connection

JH-3

NO 1

relay No. 1 contact normally open

JI-1

NC 2

relay No. 2 contact normally closed

JI-2

COM 2

relay No. 2 common connection

JI-3

NO 2

relay No. 2 contact normally open

JK-1

COM 3

relay No. 3 common connection

JK-2

NO 3

relay No. 3 contact normally open

JK-3

COM 4

relay No. 4 common connection

JK-4

NO 4

relay No. 4 contact normally open

JK-5

COM 5

relay No. 5 common connection

JK-6

NO 5

relay No. 5 contact normally open

JL-1

COM 6

relay No. 6 common connection

JL-2

NO 6

relay No. 6 contact normally open

JL-3

COM 7

relay No. 7 common connection

JL-4

NO 7

relay No. 7 contact normally open

JL-5

COM 8

relay No. 8 common connection

JL-6

NO 8

relay No. 8 contact normally open

YB

PRG

not used

C2-1

VCC

not used

C2-2

GND

not used