C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL

Page

48

PF72

Floating
condensation
offset

Floating condensation
temperature variation offset

0.0

-20.0

20.0

°C

IS-F

PF73

Set floating
condensation
min.

Minimum floating
condensation limit value

30.0

10.0

45.0

°C

IS-F

PF74

Set floating
condensation
max.

Maximum floating
condensation limit value

40.0

10.0

45.0

°C

IS-F

PF78

Side band step
overlap

Fan side band step overlap
factor

0

0

100

%

IS-F

PH01

Minimum full-
scale suction

Sets the minimum full-scale
value for the suction probe

-0.5

-10.0

PH02

Bar

IS-V

PH02

Maximum full-
scale suction

Sets the maximum full-scale
value for the suction probe

7.0

PH01

45.0

Bar

IS-V

PH03

Minimum full-
scale supply

Sets the minimum full-scale
value for the supply probe

0.0

-10.0

PH04

Bar

IS-V

PH04

Maximum full-
scale supply

Sets the maximum full-scale
value for the supply probe

30.0

PH03

45.0

Bar

IS-V

PH05

System ON/OFF
from keypad

Enables switching the
machine on/off by pressing
the ESC key

YES

NO (0)

YES (1)

IS-V

PH06

Circuit ON/OFF
from keypad

Enables switching circuits
on/off by pressing the
relevant key

NO

NO (0)

YES (1)

IS-V

PH07

System ON/OFF
from DI

Enables switching the
machine on/off from the
digital input

NO

NO (0)

YES (1)

IS-V

PH08

Circuits ON/OFF
from DI

Enables switching circuits
on/off from the relevant
digital input

NO

NO (0)

YES (1)

IS-V

PH09

System ON/OFF
from supervisor

Enables switching the
machine on/off from the
supervisor

NO

NO (0)

YES (1)

IS-V

PH10

Circuits ON/OFF
from supervisor

Enables switching circuits
on/off from the supervisor

NO

NO (0)

YES (1)

IS-V

PH11

Modbus address

Card Modbus address

1

1

247

IS-V