C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL

Page

55

PG22

Circuit 3 inverter
comp. enable

Enables the compressor
with circuit 3 inverter

NO

NO (0)

SO (0)

CO-W

Visible if PG01
> 2

PG30

Enable unique
condensation

Sets unique condensation
for the fan unit

NO

NO (0)

YES (1)

CO-W

Dual – triple
circuits only

PG32

Fan safety device

Enables the fan thermal
safety device

YES

NO (0)

YES (1)

CO-W

PG41

Number of fans
for Circuit 1

Sets the number of fans for
circuit 1

2

0

12

CO-W

Default = 3
Max = 8

on C-PRO
MEGA RACK

PG42

Circuit 1 fan
inverter enable

Enables the fan with circuit
1 inverter

NO

NO (0)

YES (0)

CO-W

PG45

Number of fans
for Circuit 2

Sets the number of fans for
circuit 2

2

0

12

CO-W

Default = 0
Max = 8

on C-PRO
MEGA RACK;
Visible if PG01
> 1 and PG30 =
0

PG46

Circuit 2 fan
inverter enable

Enables the fan with circuit
2 inverter

NO

NO (0)

YES (0)

CO-W

Visible if PG01
> 1 and PG30 =
0

PG51

Number of fans
for Circuit 3

Sets the number of fans for
circuit 3

0

0

12

CO-W

Max = 8
on C-PRO
MEGA RACK;
Visible if PG01
> 2 and PG30 =
0

PG52

Circuit 3 fan
inverter enable

Enables the fan with circuit
3 inverter

NO

NO (0)

YES (0)

CO-W

Visible if PG01
> 2 and PG30 =
0

PH20

Circuit 1 system
type or control
unit type

Sets the type of control unit
for the first circuit*:
0: -
1: BT
2: TN
3: AT

-

- (0)

AT (3)

CO-Pa

* In the case of
a single circuit
system the
parameter sets
the system type

PH21

Circuit 2 control
unit type

Sets the type of control unit
for the second circuit:
0: -
1: BT
2: TN
3: AT

-

- (0)

AT (3)

CO-Pa

Visible if PG01
> 1

PH22

Circuit 3 control
unit type

Sets the type of control unit
for the third circuit:
0: -
1: BT
2: TN
3: AT

-

- (0)

AT (3)

CO-Pa

Visible if PG01
> 2

PH27

Home page

Selects the home page to be
displayed at machine
startup:
0: Global
1: Circuit1
2: Circuit 2*
3: Circuit 3*

Global

(0)

Global

(0)

Circuit 3

(3)

CO-Pa

* If PH27=2.3
and the relevant
circuit is not
enabled,
assume a
default value of
“0”

PSd4

System builder
PSd

System builder level
password

0

-999

9999

CO-Pa

SYSTEM BUILDER MENU PARAMETERS – Compressor and fan digital output positions