C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL

Page

43

PC04

TMinOn

Minimum time for which
the compressor must remain
on, even if switching off
requested

10

0

999

Sec

IS-C

PC05

TMinOff

Minimum time for which
the compressor must remain
off, even if switching on
requested

120

0

999

Sec

IS-C

PC06

TOnOn

Minimum time that must
elapse before the same
compressor can be switched
on.

360

0

999

Sec

IS-C

PC07

TOnOther

Minimum time that must
elapse before another
compressor can be switched
on

20

0

999

Sec

IS-C

PC08

TOffOther

Minimum time that must
elapse before another
compressor can be switched
off

20

0

999

Sec

IS-C

PC09

TOnParz

Minimum time between
switching on of increments

20

0

999

Sec

IS-C

PC10

TOffParz

Minimum time between
switching off of increments

20

0

999

Sec

IS-C

PC11

Comp. probe
error Circuit 1

Number of compressors that
will be forced if an alarm
occurs on the circuit 1
suction probe

1

0

PG11

IS-C

PC31

Comp. probe
error Circuit 2

Number of compressors that
will be forced if an alarm
occurs on the circuit 2
suction probe

1

0

PG15

IS-C

Visible if PG01
> 1

PC51

Comp. probe
error Circuit 3

Number of compressors that
will be forced if an alarm
occurs on the circuit 3
suction probe

1

0

PG21

IS-C

Visible if PG01
> 2

PC69

TRestart

Minimum compressor
switch on wait time
following a system
reset/black-out

0

0

999

Sec

IS-C

PC70

Enable HP
prevention

Enable compressor
increments at high pressure
0: NO
1: YES

0 (NO)

0 (NO)

1 (SI)

IS-C

PC71

HP prevention
C1 limit SP

Set compressor increment
pressure (circuit 1)

22.0

PH03

PH04

Bar

IS-C

PC72

HP prevention
C2 limit SP

Set compressor increment
pressure (circuit 2)

22.0

PH03

PH04

Bar

IS-C

Visible if PG01
> 1