C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL

Page

40

offset. Circuit 1

of the compressor.

PC26

Inverter comp.
min. Circuit 1

Minimum compressor value
with circuit 1 inverter

0.0

0.0

100.0

%

IS-RC

Visible if PG12
= 1

PC27

Inverter comp.
speedup
Circuit 1

Compressor speedup time
with circuit 1 inverter

0

0

999

Sec

IS-RC

Visible if PG12
= 1

PC28

Inverter
compressor time
Circuit 1

Inverter ramp. Time taken
for the inverter to go from
the minimum value to the
maximum value ( circuit 1
neutral zone reg.)

10

0

999

Sec

IS-RC

Visible if PG12
= 1

PC32

Compressor min.
setpoint
Circuit 2

Minimum suction setpoint
value pertaining to the
compressors of circuit 2

0.1

PH01

SPC2

Bar

IS-RC

Visible if PG01
> 1

PC33

Compressor
max. setpoint
Circuit 2

Maximum suction setpoint
value pertaining to the
compressors of circuit 2

2.5

SPC2

PH02

Bar

IS-RC

Visible if PG01
> 1

PC34

Compressor
regulation
Circuit 2

Sets the type of regulation
for controlling the circuit 2
compressors

Neutral

Zone (1)

Side

Band (0)

Neutral

Zone (1)

IS-RC

Visible if PG01
> 1

PC36

Compressor
integral time
Circuit 2

Integral time Ti for side
band regulation of circuit 2
compressors

600

0

999

Sec

IS-RC

Visible if PG01
> 1 and PG34 =
0

PC37

Compressor
proportional
band. Circuit 2

Proportional band Bp for
side band regulation of
circuit 2 compressors

0.5

0

20.0

Bar

IS-RC

Visible if PG01
> 1 and PG34 =
0

PC38

Comp. zone
Circuit 2

Zone value for neutral zone
regulation of circuit 2
compressors

0.5

0

20.0

Bar

IS-RC

Visible if PG01
> 1 and PG34 =
1

PC39

Comp. zone
differential

Circuit 2

Differential, for neutral zone
regulation, within which the
calculation for the
insertion/release time of the
subsequent step varies.
Circuit 2

0.5

0

20.0

Bar

IS-RC

Visible if PG01
> 1 and PG34 =
1

PC40

Compressor
TOnMin
Circuit 2

Minimum insertion time for
subsequent compressor step
( circuit 2 neutral zone reg.)

20

0

PC41

Sec

IS-RC

Visible if PG01
> 1 and PG34 =
1

PC41

Compressor
TOnMax
Circuit 2

Maximum insertion time for
subsequent compressor step
( circuit 2 neutral zone reg.)

60

PC40

999

Sec

IS-RC

Visible if PG01
> 1 and PG34 =
1

PC42

Compressor
TOffMin
Circuit 2

Minimum release time for
subsequent compressor step
( circuit 2 neutral zone reg.)

10

0

PC43

Sec

IS-RC

Visible if PG01
> 1 and PG34 =
1

PC43

Compressor
TOffMax
Circuit 2

Maximum release time for
subsequent compressor step
( circuit 2 neutral zone reg.)

60

PC42

999

Sec

IS-RC

Visible if PG01
> 1 and PG34 =
1

PC44

Comp. inverter
diff.

Circuit 2

Differential for compressor
regulation with circuit 2
inverter

0.5

0.0

20.0

Bar

IS-RC

Visible if PG01
> 1 and PG16 =
1

PC45

Compressor
inverter SP
offset. Circuit 2

Suction setpoint offset for
circuit 2 inverter regulation
of the compressor.

0.0

-20.0

20.0

Bar

IS-RC

Visible if PG01
> 1 and PG16 =
1

PC46

Inverter comp.
min. Circuit 2

Minimum compressor value
with circuit 2 inverter

0.0

0.0

100.0

%

IS-RC

Visible if PG01
> 1 and PG16 =
1

PC47

Inverter comp.
speedup
Circuit 2

Compressor speedup time
with circuit 2 inverter

0

0

999

Sec

IS-RC

Visible if PG01
> 1 and PG16 =
1

PC48

Inverter
compressor time

Inverter ramp. Time taken
for the inverter to go from

10

0

999

Sec

IS-RC

Visible if PG01
> 1 and PG16 =