Parameters that can be configured on this screen follow:

PRIM. U.

: Primary on the voltage transformers. If it does not exist,

program

1

. The maximum configurable value is

999999.

SEC. U.

: Secondary on the voltage transformers. If it does not exist,

program

1

. The maximum configurable value is a 3 digit number

999.

PRIM. I.

:

Primary on the current transformer. The maximum configurable value is

30000.

PRIM. I

n

.

: Primary on the current transformer for the neutral line. The maximum

configurable value is

30000.

The default value is

5

. If it is desirable for the

CVMk2 to show the neutral line

current that is calculated, configure

0

.

Sec. I.

:

Secondary on the current transformer. It is possible to program

5

or

1

.

To store the modified parameters in memory, press

SET

and confirm with

OK

(F4). To exit without

saving changes press

ESC

(F3).

WARNING: The CVMk2 power calculation is limited according to the

following ratio:

(Prim V) x (Prim I) < 45.000.000

4.2. QUALITY

To access the power supply quality parameters configuration screen, position the cursor over

quality

and press

SET.

Two options are provided in the quality menu,

Quality

and

Events

.

CVMk2 has no battery. When supply falls down the analyzer do not store electrical

parmeters and no quality events. Is very important to guarantee the supply of the

device from an interrupted source (Batery, SAI, ...)