Relay outputs configuration – CIRCUTOR CVMk2 Series User Manual

Page 50

Advertising
background image

50

CVM

k2

CONFIGURA

TION

4.7.2.1.b Reverse configuration logic output

When a variable code corresponding to the status of an expansion card input is selected, an

alarm can be activated in one of two possible ways: direct or inverse logic.

To configure the alarms using direct logic, with respect to the input, [i.e., the alarm activates

(value = 1) when the input activates (value = 1)], the parameters should be configured as

follows:

max

= 1 and

min

= -1.

To configure the alarms using inverse logic, with respect to the input, [i.e., the alarm activates

(value = 0) when the input deactivates (value = 1)], the parameters should be configured as

follows:

max

= 0 and

min

= 0.

4.7.2.2. Relay outputs configuration

On this screen, equations are configured for the alarms that are applied to activate the system

outputs. Equations can be configured using AND (*) and/or OR (+) functions between one or

more of the 16 previously configured alarms (see Section 4.7.2.1. Alarm Configuration) in order

to activate each relay output.

To modify the card configuration parameters, press the

EDIT

button (F4). Select the output to

be configured and press

SET

to begin editing.

Press

(F3) to return to the

ALARM 01

screen (Section 4.7.2.1).

Press

(F1) to return to the

inputs

screen (Section 4.7.2.3).

WARNING: The value 00 in the outputs activation equation means that nothing

at all should be done. Thus, it should only be entered at the end of the equation.

If the value 00 is entered at the beginning of the equation, the

CVMk2 will not

make the calculation or activate the corresponding output.