Gsd modules – CIRCUTOR CVMk2 Series User Manual
Page 76

76
CVM
k2
CONFIGURA
TION
MOD
PARAMETERS
BYTE
SIZE
1
Single voltages ph-n
12
52
Phase currents
12
Phase-Phase voltages
12
Power Factor
12
Frequency
4
2
Power
48
48
3
Average values
12
44
Neutral values
8
Three-phase values
24
4
Energy
48
48
5
THD V / I
32
32
6
THD odd / even
64
64
7
Unbalanced / Asimetry / Flicker
44
44
8
Odd voltage harmonics (15º)
72
72
9
Odd current harmonics (15º)
72
72
10
Digital Input 1 / Analog Inputs 2
64
64
11
Digital Input 2 / Analog Inputs 3
64
64
12
Digital Input 3 / Analog Inputs 1
64
64
13
Cos φ
12
12
The GSD modules are configured as the table bellow.
The table shows the number of each module, the parameters inside and the total size of the
module.
4.7.7.6. GSD Modules
The limits of the Profibus protocol to charge the GSD modules are:
- Máximum 4 modules.
- Total maximum size 244 bytes.