CVM

k2

CONFIGURA

TION

4.3. DEMAND

To access the maximum demand control parameters configuration screen, position the cursor
over

DEMAND

and confirm by pressing

SET.

Parameters that can be configured on this screen follow:

Period

:

Integration window minutes used calculating the maximum demand. Values can

be programmed from

1

up to a maximum of

60.

Win. type

: It is possible to select between two window types to calculate the maximum

demand. These are:

FIXED

:

Each period duration initializes the maximum demand value. If

programmed for 15 minutes, the measured values are integrated every

15 minutes, and the values for the next 15 minutes are set to zero.

MOVING

:

The beginning and end of the integration period moves with each sample

collected. The calculation for maximum demand is made with the

values, in the integration time, each time a new sample is recorded.

To store the modified parameters in memory, press

SET

and confirm with

OK

(F4). To exit without

saving changes press

ESC

(F3).

Another example of event are showed in times period t1, t3 and t4. They are Sags. They are

configured usually unther 90% of the nominal voltage.

When the voltage goes down unther 10% it is stored as an interruption. That interruption is

showed in period t2.

Thre quality events has to be longer than 10ms. If the duration is less than 10ms, the event will

not be stored but will affect to the calculus of the average value for that period.