36

CVM

k2

CONFIGURA

TION

Example:

You wish to configure 5 tariff and assign them to

CVMk2 inputs 3, 4, 5 and 6. One expansion

card with static digital inputs is available and inserted in position 2 of the measure module.

Activate 5 tariff and configure the input corresponding to tariff 2 in input

2003

. Accordingly, input

3 in slot 2 will be defined as that which corresponds to tariff 2. The following tariff are configured

in the input: 4, 5 and 6, consecutively.

WARNING: The consecutive tariffs are automatically assigned to the inputs subsequent to the

one configured for tariff 2

4.5 DELETE

CVMk2 has a screen from which parameters, stored to the memory, can be deleted. To access
this display screen, go to the

Setup

menu. In this

menu

, access the

measure

drop-down menu.

Position the cursor over

delete

and confirm by pressing

SET

.

The following entries can be deleted in this menu:

all

.:

Delete all stored values. Values that are deleted with this option include:

maximums, minimums, energy meters, maximum demand and input pulse

meters for all of the expansion cards.

maximums

: This deletes maximum values stored with the corresponding date and time.

minimums

: This deletes minimum values stored with the corresponding date and time.

energy

.: Zero the accumulated energy meters, including those for different tariff in the

current, monthly and yearly meters.

Numbers

100X

correspond to the digital inputs for the expansion card inserted in slot 1.

Numbers

200X

correspond to the digital inputs for the expansion card inserted in slot 2, and

numbers

300X

correspond to the digital inputs for the expansion card inserted in slot 3.