Barrier plate conduit penetration, Barrier plate conduit penetration -5 – Gasboy TopKAT PLUS User Manual
Page 31

MDE-5013C TopKAT™ PLUS Installation Manual · February 2015
Page 3-5
Barrier Plate Conduit Penetration
TopKAT PLUS Installation Procedures
Figure 3-3: Conduit Layout for Electronic Pump
Electronic Pump/Dispenser
Electronic Pump/Dispenser
TopKAT PLUS
Possible Conduits
in Pedestal
Office
WAN
MCC
UPS
Optional
TCP/IP
CAT-5E
J-box
J-box
Lo
w
V
o
lt
age C
ond
uit
TCP/IP
GND
AC
L
o
w V
o
lt
age C
o
n
duit
High
V
o
lt
ag
e Con
d
u
it
Isle
Barrier Plate Conduit Penetration
The pedestal barrier plate makes the pedestal mounted TopKAT PLUS suitable for installation
over a class 1, division 2 hazardous location. Field installed conduit must run completely up
through the barrier plate. The conduit must be threaded where it passes through the barrier
plate. There must be no unused conduit openings in the barrier plate when installation is
completed. Clearance between conduits and openings in the barrier plate through which
conduit passes must not be more than 1/64-inch.