Module wiring & connections, Vcm-x component & systems wiring – Orion System VCM-X E-BUS Component User Manual
Page 107

VCM-X Component & Systems Wiring
Module Wiring & Connections
107
MHGRV-X Controller Wiring When Used With The VCM-X E-BUS
Figure 83: OE377-26-00059 MHGRV-X Controller to VCM-X E-BUS Controller Wiring
Notes:
1.)All Wiring To Be In Accordance With
Local And National Electrical Codes
and Specifications.
FILENAME
DATE:
S. Olson
DESCRIPTION:
PAGE
DRAWN BY:
JOB NAME
07/02/13
O-AAON-MHGRVX-VCMX-1A.CD
1
AAON MHGRV-X Controller
When Used With Orion VCM-X E-BUS Controller
Wiring For MHGRV-X When Used With Orion VCM-X E-BUS Controller
Line
GND
24V
AC
40 VA
Transformer
Minimum
Supply
Air Temperature
Sensor
Mount In Supply
Air Duct
RED
GRN
WHT
BLK
Condenser Valve #1
HGR Valve #1
RED
GRN
WHT
BLK
MHGRV-X CONTROLLER
(OE377-26-00059)
Set SAT
OPTIONS
Jumper Setting
to Normal.
Fan
Compressor
HGR Solenoid Valve
2 Position HGR Valve (Optional)
C1
C2
COMM
I C Cable
Connects To
Port On
Any Non VCB-X Controller Or
Expansion Module
2
I C
2
Connect
o AI2 & GND
On Main Controller
Supply Air Temperature
Sensor T