System installation, Networked multiple loop, Vcm-x component & systems wiring 18 – Orion System VCM-X E-BUS Component User Manual

Page 18

Advertising
background image

VCM-X Component & Systems Wiring

18

System Installation

5. Repeat the above steps for each local loop containing

VCM-X E-BUS Controllers with VAV/Zone Controllers.

6. The Modular System Manager can connect to any

VAV/Zone Controller on the entire system or directly

to one of the Power/Comm board’s modular output

connectors using modular cable. The Modular Service

Tool will connect to any of the controllers using the

supplied cable with DIN connectors on both ends. The

connection point on the controllers is located near the

communications connector. The Communications setting

must be set to Lo Speed Network Mode.

7. The System Manager TS II utilizes a 3 wire

communication terminal block for connection to

any controller on the communications local loop that

has communication wire terminals. Since you are using

Modular VAV/Zone Controllers, you can use a modular

pigtail connector that has a modular connector on

one end and stripped wires on the other to connect the

System Manager TS II to the Power/Comm board or one

of the Modular VAV/Zone Controllers. A separate

transformer is required for the System Manager TS II.

It has a 2 wire 24 VAC terminal block for connection to

a 24 VAC transformer. The transformer should be sized

to provide 6 VA minimum power and should be

connected using 18 gauge minimum wire.

8. The Modular Service Tool SD will connect to any

of the controllers using the supplied cable with DIN

connectors on both ends. The connection point on the

controller is located near the communications connector.

The Communications setting must be set to Lo Speed

Network

Mode.

9. Using 2 conductor shielded cable, connect from the

CommLink 5’s 3 wire communications connector to one

of the MiniLink PD’s 3 wire communications connector

marked “Network Loop”. The Loop switch on the back

of the CommLink 5 must be set to “Multiple”. The

CommLink 5 only needs to be connected to one of the

MiniLink PDs on the system.

10. Using a modular cable, connect from each MiniLink

PD’s modular connector marked “Network Loop” to

the next MiniLink PD’s “Network Loop” modular input

connector using modular cable. Connect all the

remaining MiniLink PD’s in the same manner using a

daisy chain format.

11. Before powering up the controllers, set each VAV/

Zone Controller’s board address to a unique number

from 1 through 58. Address the VCM-X E-BUS

Controller at 59. Set MiniLink PD’s address from 1 to

60.

Note: Both power and communications are transferred

from the Power/Comm board to the VAV/Zone

Controllers and the Modular System Manager.

Warning: Each Power/Comm board must have its own

24 VAC transformer for its power source. This

transformer cannot be shared with any other

board. Do not ground the transformer that is con-

nected to the Power/Comm board. The transform-

er should be sized for the required VA by using

the information found on pages 9-10 of this

manual.

Local Loops containing VCM-X E-BUS Controllers with
Non-Modular VAV/Zone Controllers

1. Using 18 gauge minimum, 2 wire cable for power, install

a 24 VAC, 8 VA minimum, transformer for the VCM-X
E-BUS Controller and wire from the transformer to the
VCM-X E-BUS Controller.

2. Using 2 conductor shielded cable, connect from the

VCM-X E-BUS Controller’s 3 wire communications

connector to the MiniLink PD’s 3 wire communications
connector marked “Local Loop”. Use 18 gauge
minimum wire for power and observe polarity on
all boards.

3. Using 2 conductor shielded cable, connect from the

VCM-X E-BUS Controller’s 3 wire communications
connector to the VAV/Zone Controllers. The VAV/Zone
Controllers connect together using modular cables from
each VAV/Zone Controller to the next controller and/or
to a Power/Comm Board. A maximum of 16 VAV/Zone
controllers are allowed per Power/Comm board. If you
have more than 16 VAV/Zone controllers, you will need
multiple Power/Comm boards. Each Power/Comm
board must have its own 24 VAC transformer sized for
the total number of VAV/Zone controllers connected to
it.

4. Repeat the above steps for each local loop containing

VCM-X E-BUS Controllers with VAV/Zone Controllers.

5. The Modular System Manager can connect to any

VAV/Zone Controller on the entire system or directly
to one of the Power/Comm board’s modular output
connectors using modular cable. The Modular Service
Tool will connect to any of the controllers using the
supplied cable with DIN connectors on both ends. The
connection point on the controllers is located near the
communications connector. The Communications setting
must be set to Lo Speed Network Mode.

6. The System Manager TS II utilizes a 3 wire

communication terminal block for connection to any
controller on the communications local loop that has
communication wire terminals. A separate transformer
is required for the System Manager TS II. It has a 2
wire 24 VAC terminal block for connection to a 24 VAC
transformer. The transformer should be sized to provide

Networked Multiple Loop

Advertising